Data Integrity - annotation of all recorded process variables with accurate data documentation. |
|
- Up to 10 PSI Overpressure on All RangesInstallation Time Minimized with Snap Track Mounting and Easy- To Access Pressure Ports and Electrical Connections
- 0 to 5 VDC or 2-wire 4 to 20mA Analog Outputs Are Compatible with Energy Management Systems
- Reverse Wiring Protection
- Internal Regulation Permits Use with Unregulated DC Power Supplies
- Fire Retardant Case (UL 94 V-0 Approved)
- Meets CE Conformance Standards
For Pricing Call Toll Free - 877-215-9090 |
Setra Systems 264 pressure transducers
sense differential or gauge (static)
pressure and convert this pressure
difference to a proportional electrical output
for either unidirectional or bidirectional
pressure ranges. The 264 Series is offered
with a high level analog 0 to 5 VDC or 4 to
20 mA output.
Used in Building Energy Management
Systems, these transducers are capable of
measuring pressures and flows with the
accuracy necessary for proper building
pressurization and air flow control.
The 264 Series transducers are available for
air pressure ranges as low as 0.1 in. W.C. full
scale to 100 in. W.C. full scale. Static standard
accuracy is ±1.0% full scale in normal ambient
temperature environments, but higher
accuracies are available. The units are
temperature compensated to 0.033% FS/oF
thermal error over the temperature range of 0° to 150°F.
The Model 264 utilizes an improved all
stainless steel micro-tig welded sensor. The
tensioned stainless steel diaphragm and
insulated stainless steel electrode, positioned
close to the diaphragm, form a variable
capacitor. Positive pressure moves the
diaphragm toward the electrode, increasing
the capacitance. A decrease in pressure
moves the diaphragm away from the
electrode, decreasing the capacitance. The
change in capacitance is detected and
converted to a linear DC electrical signal by
Setra’s unique electronic circuit.
The tensioned sensor allows up to 10 PSI
overpressure (in either direction) with no
damage to the unit. In addition, the parts that
make up the sensor have thermally matched
coefficients, which promote improved
temperature performance and excellent long
term stability.
- Specifications
- Ordering Information
- Dimensions
|